Oil / Gas steel boiler
Series TAURUS DUAL

  • with heating gas recirculation and three-pass
  • CE 0694 BM 3697

The combustion chamber has the shape of a cylinder. The burner flame burns into horizontally and the hot gases flow around the flame back into the Nachschaltfläche. The combustion chambers are flowed through directly heating water. 92% achieved at nominal load - The optimal utilization of heat depending on the load boiler efficiencies of 90th

Complete with standard control panel including safety temperature limiter, Temperature Controller, thermometer, possibility of connecting a one- or two-stage burner, and the possibility of connecting an external controller.

Model: H1
mm
H2
mm
H4
mm
H6
mm
H10
mm
L
mm
P
mm
P2
mm
P4
mm
P5
mm
P6
mm
Øb
mm
Øc
mm
N1/N2
mm
N3/N4
DN
N8
DN
70 855 415 911 415 54,5 750 994 630 240 402 200-250 130 200 50 1" 1/2"
80 855 415 911 415 54,5 750 994 630 240 402 200-250 130 200 50 1" 1/2"
90 855 415 911 415 54,5 750 1119 755 265 417 200-250 130 200 50 1" 1/2"
100 855 415 911 415 54,5 750 1119 755 265 417 200-250 130 200 50 1" 1/2"
120 855 415 911 415 54,5 750 1119 755 265 417 200-250 130 200 50 1" 1/2"
150 905 440 961 440 54,5 800 1364 1000 475 452 200-250 160 250 50 1" 1/2"
200 905 440 961 440 54,5 800 1364 1000 475 452 200-250 160 250 50 1" 1/2"


Panel:

  1. Temperature Controller
  2. Lighted main switch
  3. Safety temperature limiter
  4. Control lamp heating circulation pump(yellow)
  5. Control lamp safety temperature limiter(red)
  6. Control lamp Burner in operation (yellow)
  7. Thermometer


Dimensions


technical Data:

Type: 70 80 90 100 120 150 200
FIRING (kW) 76 87 98 109 131 163 219
NOMINAL THERMAL POWER (kW) 70 80 90 100 120 150 200
Boiler water content (ltr.) 105 105 123 123 123 172 172
Water-side resistance (mbar) 9 9 10 12 13 14 15
Heating gas side pressure drop (mbar) 0,8 1,0 0,8 1,0 1,1 1,2 1,9
max. Operating pressure (bar) 5 5 5 5 5 5 5
Weight (kg) 216 216 258 258 258 346 346