The hot water storage of the series "PS-M" are particularly suited to the installation as a heat storage in heating systems. The tanks are only painted on the outside, while the inside of the tank is untreated.
Technical features:
Model | PSM 300 | PSM 500 | PSM 800 | PSM 1000 | PSM 1500 | PSM 2000 | PSM 3000 | PSM 5000 |
---|---|---|---|---|---|---|---|---|
Size liter | 290 | 490 | 732 | 925 | 1.515 | 2.054 | 2.960 | 5.055 |
Height with isolation mm | 1.357 | 1.630 | 1.760 | 2.090 | 2.200 | 2.420 | 2.700 | 2.950 |
Diameter without isolation mm | 550 | 650 | 790 | 790 | 1.000 | 1.100 | 1.250 | 1.600 |
Diameter with isolation mm | 650 | 750 | 990 | 990 | 1.200 | 1.300 | 1.450 | 1.800 |
Operating pressure bar | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 |
Max. operating temperature | 95°C | 95°C | 95°C | 95°C | 95°C | 95°C | 95°C | 95°C |
Dimension, tilted mm | 1.505 | 1.794 | 1.740 | 2.090 | 2.215 | 2.450 | 2.705 | 3.010 |
Weight kg | 57 | 79 | 97 | 114 | 162 | 225 | 280 | 504 |
Instructions for installation:
Plastics are subject to temperature fluctuations. The insulation must therefore be stored for at least 24 hours at room temperature (not below 15 ° C) in order to avoid damage during installation! Place the insulation around the storage tank and fix it with tension belts if necessary. Tap from the back in the direction of the zipper until the rows of fasteners are so close that they can be easily closed. DO NOT USE TOOLS! If zippers are damaged during assembly, the entire insulation must be replaced at a cost.