The systems provide without long heating for instant heat and are suitable for halls of any kind (production halls, workshops, greenhouses, etc.) The Stand air heater can be operated with oil or gas burner. Posing indoors only.
The Stand air heaters have a safety thermostat with manual reset, and switch box with motor protection switch, indicator lights, summer / winter switch
Model | GG 30 | GG 40 | GG 60 | GG 80 | GG 110 | GG 130 | GG 160 | GG 200 | GG 250 | GG 300 | GG 350 | GG 400 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
CE-Certification No. | 2078 | ||||||||||||
Firing power | kW | 34 | 46 | 69 | 93 | 127 | 151 | 186 | 232 | 290 | 348 | 407 | 465 |
Nominal heat output | kW | 31,5 | 42,4 | 63,3 | 84,9 | 115,5 | 136,9 | 167,9 | 210,2 | 263,6 | 317,7 | 372,8 | 427,3 |
Efficiency | % | 92,7 | 92,2 | 91,8 | 91,3 | 91,0 | 91,0 | 91,0 | 91,0 | 91,0 | 91,3 | 91,6 | 91,9 |
Airflow | m³/h | 2400 | 3000 | 4500 | 6500 | 8200 | 9600 | 12300 | 14800 | 18000 | 24000 | 28000 | 32000 |
max. ext. Pressure | Pa | 180 | 280 | 240 | 200 | 180 | 330 | 240 | 240 | 350 | 300 | 330 | 350 |
Temperature increase | °C | 38 | 41 | 41 | 38 | 41 | 42 | 40 | 42 | 43 | 39 | 38 | 38 |
Number of fans | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 3 | 3 | |
R.p.m. | 900 | 1200 | 740 | 660 | 630 | 630 | 560 | 700 | 630 | 630 | 630 | 630 | |
Electrical connection | Volt | 230 | 230 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 |
Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |
W | 0,36 | 0,55 | 0,75 | 1,50 | 1,50 | 2,20 | 2,20 | 4,00 | 4,00 | 5,50 | 6,60 | 8,50 | |
Sound level (Distance 6 mtr.) | db | 58 | 62 | 60 | 63 | 59 | 65 | 63 | 58 | 65 | 63 | 64 | 63 |
Weight (without burner) | kg | 110 | 150 | 200 | 260 | 310 | 430 | 520 | 580 | 690 | 850 | 1080 | 1300 |
above mentioned data refer to: inlet air temperature: + 20 °
Model | GG 30 | GG 40 | GG 60 | GG 80 | GG 110 | GG 130 | GG 160 | GG 200 | GG 250 | GG 300 | GG 350 | GG 400 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Length Flame tube | min. mm | 110 | 110 | 120 | 120 | 120 | 120 | 120 | 120 | 120 | 120 | 120 | 120 |
max. mm | 180 | 200 | 210 | 210 | 230 | 230 | 260 | 260 | 260 | 260 | 310 | 330 | |
max. Ø Flame tube | mm | 105 | 105 | 105 | 135 | 135 | 155 | 155 | 175 | 175 | 195 | 195 | 195 |
Backpressure in combustion chamber | Pa | 3 | 15 | 22 | 30 | 35 | 41 | 50 | 62 | 78 | 112 | 132 | 150 |
Flange ØB | mm | 110 | 110 | 110 | 140 | 140 | 160 | 160 | 180 | 180 | 200 | 200 | 200 |
Model | GG 30 | GG 40 | GG 60 | GG 80 | GG 110 | GG 130 | GG 160 | GG 200 | GG 250 | GG 300 | GG 350 | GG 400 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
A | mm | 750 | 750 | 900 | 900 | 1000 | 1000 | 1400 | 1400 | 1900 | 1900 | 2100 | 2100 |
B | mm | 500 | 500 | 650 | 650 | 850 | 850 | 1000 | 1000 | 1150 | 1150 | 1250 | 1250 |
C | mm | 1600 | 1600 | 1800 | 1800 | 2100 | 2100 | 2300 | 2300 | 2400 | 2400 | 2450 | 2450 |
D | mm | 130 | 130 | 130 | 130 | 130 | 130 | 130 | 130 | 130 | 130 | 130 | 130 |
E | mm | 475 | 475 | 545 | 545 | 640 | 640 | 750 | 750 | 670 | 670 | 820 | 820 |
F | mm | 760 | 760 | 930 | 930 | 1095 | 1095 | 1155 | 1155 | 1155 | 1155 | 1235 | 1235 |
G | mm | 1235 | 1235 | 1440 | 1440 | 1730 | 1730 | 1905 | 1905 | 2005 | 2005 | 2080 | 2080 |